Sizing your System
, Inverter and Generator
Packaged System Sizing
Sw series inverters ( True Sinewave ) are the
premium line and the DR series (Modified Sinewave) are listed Below.
SW Series
Backup Electric System
|
Backup Electric System |
2000 SW |
4000SW |
5000SW |
8000SW |
10,000SW |
| Trace™ Inverter Model |
SW2512/S |
SW4048/S |
SW5548/S |
SW4048/D |
SW5548/D |
| ACOutput Voltage |
120 VAC |
120 VAC |
120 VAC |
120 VAC |
120 VAC |
|
System Rating |
2000 watts |
4000 watts |
5000 watts |
8000 watts |
10,000 watts |
| Continuous Power |
2500 VA |
4000 VA |
5500 VA |
8000 VA |
11,000 Va |
| Maximum Power |
7200 watts |
9400 watts |
9400 watts |
18,700 watts |
18,700 watts |
| Nominal Input Voltage |
12 VDC |
48 VDC |
48 VDC |
48 VDC |
48 VDC |
| Max. Charging Current |
150 amps |
60 amps |
75 amps |
120 amps |
150 amps |
| Max. Charging Power |
1800 watts |
2800 watts |
3600 watts |
5760 watts |
7200 watts |
| Number of AC inputs |
|
|
2 |
|
|
| Transfer Relay Rating |
|
|
60 amps |
|
|
| Transfer Time (typical) |
|
|
16 ms |
|
|
| Transfer Time (max) |
|
|
34 ms |
|
|
| AC Output Waveform |
|
|
sinewave |
|
|
| Voltage Regulation |
|
|
+/- 2% |
|
|
| Frequency Regulation |
|
|
+/- 0.04 % |
|
|
| Automatic Transfer |

|

|

|

|

|
| 3-Stage Battery Charger |

|

|

|

|

|
| Generator Starting |

|

|

|

|

|
| Generator Support |

|

|

|

|

|
| Utility Sell Back |

|

|

|

|

|
| PLC* Compatible |

|

|

|
|
|
|
Battery Bank Sizing |
Minimum Size
2 hours at 1/2 rated power |
2 KWh** |
4 KWh** |
5 KWh** |
8 KWh** |
10 KWh** |
Standard Size
8 hours at 1/2 rated power |
8 KWh** |
N/A |
20 KWh** |
N/A |
40 KWh** |
|
Generator Guidelines |
| Minimum Size |
4.0 KW |
5.0 KW |
6.0 KW |
8.5 KW |
11.0 KW |
| Recommended Size |
8.5 KW |
8.5 KW |
8.5 KW |
11.0 KW |
17.0 KW |
*Power line carrier control system for
home automation use
** Battery bank may be increased in size to meet longer run time
requirements |
Lower-Cost
Backup Backup Electric System
|
Backup Electric System |
400TS |
1000DR |
2000DR |
3000DR |
| Trace™ Inverter Model |
TS512SB |
DR1524 |
DR2424 |
DR3624 |
| Ac Output Voltage |
120VAC |
120VAC |
120VAC |
120VAC |
|
System Rating |
400 watts |
1000 watts |
2000 watts |
3000 watts |
| Continuous Power |
500 VA |
1500 VA |
2500 VA |
3600 VA |
| Maximum Power |
1900 watts |
4800 watts |
8600 watts |
12,000 watts |
| Nominal Input Voltage |
12 VDC |
24 VDC |
24 VDC |
24 VDC |
| Max. Charging Current |
15 amps |
35 amps |
70 amps |
70 amps |
| Max. Charging Power |
180 watts |
840 watts |
1680 watts |
1680 watts |
| Number of AC inputs |
1 |
|
1 |
|
| Transfer Relay Rating |
15 amps |
|
30 amps |
|
| Transfer Time (typical) |
16 ms |
|
16 ms |
|
| Transfer Time (max) |
34 ms |
|
34 ms |
|
| AC Output Waveform |
modified SW |
|
modified sinewave |
|
| Voltage Regulation |
+/- 10% |
|
+/- 5% |
|
| Frequency Regulation |
+/- 0.04% |
|
+/- 0.04 % |
|
| Automatic Transfer |

|

|

|

|
| 3-Stage Battery Charger |

|

|

|

|
| Generator Starting |
|
|
|
|
| Generator Support |
|
|
|
|
| Utility Sell Back |
|
|
|
|
| PLC* Compatible |
|
|
|
|
|
Battery Bank Sizing |
Minimum Size
2 hours at 1/2 rated power |
400 Wh** |
1 KWh** |
2 KWh** |
3 KWh** |
Standard Size
8 hours at 1/2 rated power |
1.6 KWh** |
4 KWh** |
8 KWh** |
12 KWh** |
|
Generator Guidelines |
| Minimum Size |
900 watts |
4.0 KW |
6.0 KW |
6.0 KW |
| Recommended Size |
2.0 KW |
8.5 KW |
8.5 KW |
11.0 KW |
*Power line carrier control system for
home automation use
** Battery bank may be increased in size to meet longer run time
requirements |
|
Please email us with any questions you have.

|